3. Practical Electricity
Open the simulation and work through each chapter. Write your prediction before you run the test.
a. Electrical power
Predict
A 2200 W kettle element (24 Ω) is replaced by a 12 Ω element on the same 230 V supply. Predict the new power.
Test: recording table
| Appliance | P / W | I = P/V / A | R = V²/P / Ω |
|---|---|---|---|
Pattern I found:
Challenge
Choose the kettle element so that it heats 1.0 kg of water from 30 °C to 100 °C in 2.0 minutes (294 000 J needed). Assume no energy is lost.
Exam practice
- A rice cooker draws 3.0 A from the 230 V mains. Calculate its power. [2]
- A 1000 W iron is connected to 230 V mains. Calculate the current in it. [2]
- A heating element of resistance 50 Ω carries a current of 4.0 A. Calculate the power transferred. [2]
b. Energy and cost
Predict
Which costs more per month: 1.0 kW air-con for 8 h/day, or 3.0 kW water heater for 0.5 h/day?
Test: recording table
| Appliance | Power / kW | Hours per day | kWh per month | Cost per month |
|---|---|---|---|---|
Pattern I found:
Challenge
Change the hours of use so that the household’s monthly bill (30 days, before GST) is below S$100.00 (generic mode: the equivalent of 350 kWh). The refrigerator must stay on 24 hours a day.
Exam practice
- A 2.2 kW kettle is used for 15 minutes each day. Calculate the energy it uses in 30 days, in kWh. [2]
- Electricity costs 28.59 cents per kWh. Calculate the cost of running a 150 W refrigerator for 24 hours a day for 30 days, in dollars. [3]
- How many joules are there in 1 kWh? [1]
c. Mains wiring and hazards
Predict
Which single wire is most dangerous to touch: live, neutral or earth? Why?
Test: recording table
| Wire | Colour | Letter | Plug terminal | p.d. to earth / V |
|---|---|---|---|---|
Pattern I found:
Challenge
Wire the plug for a 2200 W kettle correctly and fit the correct fuse. (Use Real view to wire the plug.)
Exam practice
- What is the colour of the insulation on the earth wire? [1]
A Brown
B Blue
C Green and yellow stripes
D RedAnswer: ____
- Which wire is at a high alternating p.d. relative to the ground? [1]
A Live
B Neutral
C Earth
D None of themAnswer: ____
- Why is it dangerous to use a hair dryer with wet hands? [1]
A Water increases the mains p.d.
B Wet skin has a lower resistance, so a larger current can flow through the body
C Water makes the fuse blow
D The hair dryer uses more powerAnswer: ____
d. Fuses and circuit breakers
Predict
2200 W kettle on a 13 A fused extension; an 1800 W hair dryer is added. Predict what happens.
Test: recording table
| Appliance | Power / W | Current / A | Fuse chosen / A |
|---|---|---|---|
Pattern I found:
Challenge
Choose the correct plug fuse for each appliance (230 V mains).
Exam practice
- A 230 V hair dryer is rated 1800 W. Calculate its normal current. [2]
- Which fuse should be fitted to the plug of the 1800 W hair dryer? [1]
A 3 A
B 5 A
C 13 A
D 30 AAnswer: ____
- Why are fuses fitted in the live wire rather than the neutral wire? [1]
A The live wire carries more current
B So that when the fuse blows the appliance is disconnected from the high p.d.
C The neutral wire is too thin
D So that the fuse blows more easilyAnswer: ____
e. Earthing and faults
Predict
Fault 1: earthed metal kettle + 13 A fuse, live touches casing. Fault 2: same but earth wire missing. Predict what happens in each.
Test: recording table
| Earth | Fuse | Casing | Casing p.d. / V | Person current / mA | Safe? |
|---|---|---|---|---|---|
Pattern I found:
Challenge
With the fault switched on, find two different arrangements that keep the person safe (no current through them) and leave nothing overheating.
Exam practice
- What is the main purpose of the earth wire? [1]
A To carry the normal current back to the supply
B To provide a low-resistance path to the ground for a fault current
C To make the fuse blow during normal use
D To reduce the p.d. of the mainsAnswer: ____
- A hair dryer has a plastic casing and the symbol ⧈. Why does it not need an earth wire? [1]
A It uses very little current
B It is double insulated: the casing is an insulator so it cannot become live
C Its fuse is in the neutral wire
D Plastic conducts the current to earthAnswer: ____
- In a fault, the live wire touches an earthed metal casing. The total resistance of the fault path is 0.80 Ω. Calculate the fault current from 230 V mains. [2]